Operating Instructions – Electronic Motor DRC.-..-DAC
181
10
Local mode
Operation
10.2 Local mode
10.2.1 Activating local mode
When setting the signal at binary input DI04 to "1", binary inputs DI01 to DI03 are used
for local mode with the following functions:
10.2.2 Deactivating local mode
10.2.3 Error reset in local mode
In local mode, an error can be reset as follows:
An error is reset when you have set binary inputs DI01 and DI02 to "1" and a rising edge
occurs at binary input DI03 = "0"
→
"1".
Binary input
Functionality
Easy mode
(see chapter "Startup")
In conjunction with expert mode and
deactivated controls f1/f2
(see chapter "Startup")
DI01
CW/stop
DI02
CCW/stop
DI03
Setpoint selection
"0" = Setpoint potentiometer f1 active
"1" = Setpoint switch f2 active
Setpoint selection
"0" = Setpoint n_f1 active (parameter
10096.35, factory set to 1500 rpm)
"1" = Setpoint n_f2 active (parameter
10096.36, factory set to 200 rpm)
DI04
Switching between local mode / automatic mode
WARNING
Risk of injury if the drive starts up unintentionally.
Severe or fatal injuries.
• Before deactivating local mode, take measures to prevent the drive unit from
starting up unintentionally, e.g. activate "STO".
• Take additional safety precautions depending on the application to avoid injury to
people and damage to machinery.