Operating Instructions – Electronic Motor DRC.-..-DAC
89
6
Startup with double slave GLK31A
Startup
Assigning the
slave address
using a hand-held
programming
device
Hand-held AS-Interface programming devices offer the following functions:
• Reading out and changing an AS-Interface slave address
• Reading out the AS-Interface profile
• Reading out and changing the data and parameter bits
• Function check and test run.
When using a hand-held programming device, you need a
2-core
connection cable that
fits onto the AS-interface plug connector of the DRC drive unit (see the following figure).
X4271: AS-Inter-
face communica-
tion interface
The following table informs about this connection:
NOTICE
Damage to the units caused by faulty installation
Possible damage to property
• The hand-held programming device may
only
be connected via pins 1 "AS-
Int" and 3 "AS-Interface –" with the AS-Interface plug connector. The hand-
held programming device can be damaged if not connected properly.
Function
Connection of AS-Interface data cable
Connection type
M12, 4-pole, male, A-coded
Wiring diagram
2384154763
Assignment
No.
Name
Function
1
AS+
AS-Interface data cable +
2
n.c.
Not connected
3
AS
−
AS-Interface data cable –
4
n.c.
Not connected
2
1
4
3
00
I