Operating Instructions – MOVIDRIVE® MDR60A/61B
129
16
Smallest wire bending space (EN 61800-5-1)
Technical Data – Basic Unit
16.4 Smallest wire bending space (EN 61800-5-1)
As stipulated in EN 61800-5-1, the distance between a power connection terminal and
an obstruction toward which the wire is directed on leaving the terminal must correspond
with the minimum values given in the table below.
Cable cross section in mm
2
Smallest wire bending space in mm
Wires per connection terminal
1
2
3
10 ... 16
40
-
-
25
50
-
-
35
65
-
-
50
125
125
180
70
150
150
190
95
180
180
205
120
205
205
230
150
255
255
280
185
305
305
330
240
305
305
380