General technical data
Technical Data – Basic Unit
16.2 General technical data
16.2.1 MOVIDRIVE
®
MDR60A regenerative power supply unit
MOVIDRIVE
®
MDR60A
0150-503-00 (size 2)
0370-503-00 (size 3)
0750-503-00 (size 4)
1320-503-00 (size 6)
Interference immunity
Meets EN 61800-3
Meets EN 61000-6-1 and EN 61000-6-2
Interference emission with
EMC-compliant installation
Meets EN 61800-3:
•
with NF035-503 line filter (MDR60A0150-503-00)
•
with NF048-503 line filter (MDR60A0150-503-00)
•
with NF085-503 line filter (MDR60A0370-503-00)
•
with NF150-503 line filter (MDR60A0750-503-00)
Meets EN 61000-6-4 with NF300503 line
filter
Ambient temperature
ϑ
U
Ambient temperature derating
0 °C – +40 °C
I
N
reduction: 3% I
N
per K to max. 60 °C
0 °C – +40 °C
I
N
reduction: 3% I
N
per K to max. 55 °C
Climate class
EN 60721-3-3, class 3K3
Storage temperature
1)
ϑ
L
1) In case of long-term storage, connect the unit to the power supply for at least 5 minutes every two years, otherwise the unit's service
life may be reduced.
–25 °C – +70 °C (EN 60721-3-3, class 3K3)
–25 °C – +55 °C
(EN 60721-3-3, class 3K3)
Cooling type (DIN 51751)
Forced cooling
(temperature-controlled fan, response threshold 50 °C)
Forced cooling
(temperature-controlled fan, response
threshold 45 °C)
Degree of protection size 2
EN 60529 size 3
(NEMA1) size 4
IP20
IP20
IP00 (power connections)
IP10 (power connections)
•
With fitted plexiglass cover supplied as standard
•
With fitted shrink tubing (not included in scope of
delivery)
IP20
•
with mounted DLB11B touch guard
IP20
Operating mode
Continuous duty (EN 60149-1-1 and 1-3)
Overvoltage category
III according to IEC 60664-1 (VDE 0110-1)
Pollution class
2 according to IEC 60664-1 (VDE 0110-1)
Installation altitude
At h
≤
1000 m without restrictions.
The following restrictions apply to heights
≥
1000:
•
From 1000 m to max. 4000 m:
–
I
N
reduction by 1% per 100 m
•
from 2000 m (6562 ft) to max. 4000 m (13120 ft):
–
The safe disconnection of power and electron-
ics connections can no longer be assured
above 2000 m.
This requires external measures (IEC 60664-1/
EN 61800-5-1).
–
You have to connect an overvoltage protection
device in order to reduce the overvoltages from
category III to category II.
h
≤
1000 m: No limitation
From 1000 m to max. 4000 m:
I
N
reduction: 0.5% per 100 m
P
i
f
kVA
Hz