General technical data
Technical Data – Basic Unit
16.2.2 MOVIDRIVE
®
MDR61B regenerative power supply unit
MOVIDRIVE
®
MDR61B
1600-503-00/L (size 7)
2500-503-00/L (size 7)
Interference immunity
Meets EN 61800-3
Interference emission with
EMC-compliant installation
Meets EN 61800-3:
•
with NF600-503 line filter
Ambient temperature
ϑ
U
Ambient temperature derating
0 °C – +50 °C with I
D
= 100 % I
ZK
0 °C – +40 °C with I
D
= 125 % I
ZK
2.5 % I
ZK
per K between 40 °C – +50 °C
3 % I
ZK
per K between 50 °C – +60 °C
Climate class
EN 60721-3-3, class 3K3
Storage temperature
1)
ϑ
L
1) In case of long-term storage, connect the unit to the power supply for at least 5 minutes every two years, otherwise the unit's service
life may be reduced.
–25 °C – +70 °C (EN 60721-3-3, class 3K3)
Cooling type (DIN 51751)
Forced cooling
(temperature-controlled fan, response threshold 50 °C)
Degree of protection
EN 60529
(NEMA1)
IP00
IP10 (power connections)
•
with mounted DLB31B touch guard
Operating mode
Continuous duty (EN 60149-1-1 and 1-3)
Overvoltage category
III according to IEC 60664-1 (VDE 0110-1)
Pollution class
2 according to IEC 60664-1 (VDE 0110-1)
Installation altitude
At h
≤
1000 m without restrictions.
The following restrictions apply to heights
≥
1000:
•
From 1000 m to max. 4000 m:
–
I
N
reduction by 1% per 100 m
•
from 2000 m (6562 ft) to max. 4000 m (13120 ft):
–
The safe disconnection of power and electronics connections can no longer be assured
above 2000 m.
This requires external measures (IEC 60664-1/EN 61800-5-1).
–
You have to connect an overvoltage protection device in order to reduce the overvoltages
from category III to category II.