Operating Instructions – MOVIDRIVE® MDR60A/61B
73
6
Explanation of the parameters
MDR61B1600/2500 – Parameters
P43x Current refer-
ence signal
Signal if the line current is greater than or less than the reference value.
P430 Current ref-
erence value
Setting range: 0 – 100 – 150 % I
N
P431 Hysteresis
Setting range: 0 – 5 – 30% I
N
P432 Delay time
Setting range: 0 – 1 – 9 s
P433 Signal = “1“
if:
I < I
ref
/ I > I
ref
6.2.6
P6xx Terminal assignment
P60x Binary inputs
of basic unit
The binary inputs are not programmable.
Binary input DIØØ with fixed assignment "/CONTROLLER INHIBIT".
P600 Binary
input DIØ1
• P600 Binary input DIØ1 "ENABLE"
P601 Binary
input DIØ2
• P601 Binary input DIØ2 "RESET"
• DIØ3 – DIØ7 no function
P62x Binary out-
puts of basic unit
278446603
I
ref
-I
ref
P4
3
1
P4
3
0
t
P4
3
2
1
1
0
0
t
t
P4
33
:
S
ign
a
l = "1" if i | I | < I
ref
P4
33
:
S
ign
a
l = "1" if i | I | > I
ref
I
%
of I
N
INFORMATION
The binary signals are only valid if the unit has signaled "ready" after switch-on and
there is no error display. Binary signals have "0" status while MOVIDRIVE
®
is being
initialized.
Several terminals can be assigned the same function.