6
Explanation of the parameters
MDR61B1600/2500 – Parameters
P620 – P623
binary output
DOØ1 – DOØ4
The following functions can be assigned to the freely programmable binary outputs:
• /FAULT
• READY FOR OPERATION
• OUTPUT STAGE ON
• CURRENT REFERENCE SIGNAL
• SIZE 7 READY FOR POWER ON
6.2.7
P8xx Unit functions
P80x Setup
P802 Factory set-
ting
Setting range: NO / DELIVERY STATUS
The "delivery state" setting also resets the data listed above.
An "8" appears on the 7-segment display during reset. The previous operating state of
the inverter appears on the display after the factory settings have been restored.
P802
automatically reverts to "NO".
P803 Parameter
lock
Setting range: ON / OFF
Setting
P803
to "ON" makes it possible to prevent any change to the parameters (except
for
and the parameter lock itself). This makes sense, for example,
after the regenerative power supply unit has been optimized.
P803
must be set to "OFF"
to enable changes to parameters again.
The parameter lock does not have any effect on the following parameters:
•
P803 Parameter lock
•
P804 Reset statis-
tics data
Setting range: NO / FAULT MEMORY / kWh COUNTER / OPERATING HOURS
P804
permits reset of the statistics data stored in the EEPROM, namely the fault mem-
ory, kilowatt-hour meter and operating hours counter.
P81x Serial communication
P810 RS485
address
Setting range: 0 – 99
P810
sets the address by means of which communication can take place with the re-
generative power supply unit via the serial interfaces. A maximum of 32 stations can be
interconnected.
P811 RS485 group
address
Setting range: 100 – 199
P811
makes it possible to group together several MOVIDRIVE
®
B units for communica-
tion via the serial interface. In this way, all MOVIDRIVE
®
B units with the same RS485
INFORMATION
Save the set parameter values with SHELL or the DBG60B keypad before you start
resetting the parameters. After resetting, it is necessary to adapt the altered parameter
values and terminal assignments to meet the requirements.
INFORMATION
The regenerative power supply unit is always delivered with the address set to 0. To
avoid problems during data exchange in serial communication with several inverters,
we recommend that you do not use address 0.