Operating Instructions – MOVIDRIVE® MDR60A/61B
77
6
Explanation of the parameters
MDR61B1600/2500 – Parameters
P876 PO data
enable
Setting range: ON / OFF
• ON: The process output data that was last sent from the fieldbus controller becomes
effective.
• OFF: The last valid process output data remain in effect.
P88x Serial communication SBus 1/2
P881 Address
SBus 1
Setting range: 0 – 63
Use
P881
to set the system bus address of MOVIDRIVE
®
B. MOVIDRIVE
®
B can com-
municate with other MOVIDRIVE
®
B units via the system bus (SC11) by means of the
address set here.
P883 Timeout
delay SBus 1
Setting range: 0 – 650 s
P883
is used to set the monitoring time for data transmission via system bus. If there is
no data traffic via the system bus during the time period set in
P883
, MOVIDRIVE
®
will
execute the error response set in
. No monitoring of
data transmission via the system bus takes place when
P883
is set to the value 0.
P884 Baud rate
SBus 1
Setting range: 125 / 250 / 500/1000 kBaud
P884 sets the transmission speed of the system bus.
INFORMATION
If the process data assignment is changed,
P876
is automatically set to "OFF".