Operating Instructions – MOVIAXIS® MX Multi-Axis Servo Inverter
6
Displays of the supply and axis modules
Operation
Responses to
error acknow-
ledgement
CPU reset
A true restart of the microcontroller and the firmware will take place in case of a CPU
reset. The firmware system is started as though a new axis module has been connected
to the network.
Restart of the system has the following results:
• The bootstrap loader will be activated, "b0" will appear in the display,
• Reference positions of incremental encoder systems will be lost,
• Any existing fieldbus interfaces will be reset,
• Any existing control options will be reset,
• Fieldbus communication will be interrupted,
• The interface between options and firmware system is initialized again. A new boot
synchronization to the fieldbus or control option takes place.
• Communication via CAN interfaces of the system will be interrupted,
• Connection to the supply module will be synchronized again (hardware information
system),
• The existing "error message" will be reset [binary output = 1, system status = 0].
The ready signal will be reset by the system status control after the reset by the system
status control.
System restart
There will be
no
true reset of the microcontroller with a system restart.
The system restart has the following results:
• The firmware will be restarted, without the boot loader becoming active
(no display "b0" !)
• Reference positions of incremental encoder systems will be lost,
• Any existing fieldbus cards are not affected,
• Any existing control options are not affected,
• The interface between options and firmware system is initialized again. A new boot
synchronization to the fieldbus or control option takes place.
• Communication via CAN interfaces of the system will be interrupted,
• Connection to the supply module will be synchronized again (hardware information
system),
• The existing "error message" will be reset [binary output = 1, system status = 0].
The ready signal will be reset by the system status control after the reset by the system
status control.
Warm start
A warm start only resets the error code.
The warm start has the following results:
• The firmware system is not rebooted
• All reference positions will be maintained
• Communication is not interrupted
• The existing "error message“ will be reset [binary output = 1, system status = 0].