Operating Instructions – MOVIAXIS® MX Multi-Axis Servo Inverter
171
6
Operating displays and errors of MXA axis module
Operation
42
Error "Following
error positioning“
A preset, maximum permitted follow-
ing error was exceeded during posi-
tioning
•
Encoder connected incorrectly
•
Acceleration ramps too short
•
P component of positioning con-
troller too small
•
Incorrectly set speed controller
parameters
•
Value of lag error tolerance too
small
Output stage
inhibit
System is
waiting
Warm start
Yes
Ready = 1
Malfunction
= 0
01
FCB Positioning: Lag error
43
Error "Remote
timeout“
An interruption has occurred during
control via a serial interface
Shutdown with
application limits
System is
waiting
Warm start
Yes
Ready = 1
Malfunction
= 0
01
FCB Jog mode: Communication time-
out at direction control
44
Error "Ixt utiliza-
tion“
Overload in inverter
Output stage
inhibit
System is
waiting
Warm start
Yes
Ready = 1
Malfunction
= 0
01
Ixt current limit less than required d-
current
02
Limit chip temperature difference
exceeded
03
Limit chip temperature exceeded
04
Limit electromechanical utilization
exceeded
05
Short circuit of sensor detected
06
Motor current limit exceeded
07
AD conversion has not taken place
45
Error "System
initialization“
Error during initialization of the sys-
tem
Output stage
inhibit
System
locked / CPU
reset
Yes
Ready = 0
Malfunction
= 0
01
The measured current offsets are out-
side the permitted limit values
02
An error occurred during CRC gener-
ation for the firmware
03
Data bus error during RAM test
04
Address bus error during RAM test
05
Memory cell error during RAM test
46
Error "Timeout
SBUS#2"
Communication via SBUS #2 is inter-
rupted
Shutdown with
application limits
[P]
System is
waiting
Warm start
Yes
Ready = 1
Malfunction
= 0
01
Timeout CANopen CAN2
50
Error 24V supply
voltage
Error in 24V supply voltage
Output stage
inhibit
System is
blocked
System restart
yes, if
system
is ready
Ready = 0
Malfunction
= 0
01
24V signals incorrect or switched-
mode power supply defective
51
Error "Software
limit switch“
A software limit switch was
approached during positioning
Shutdown with
emergency stop
delay (D), (P)
System is
waiting
Warm start
Yes
Ready = 1
Malfunction
= 0
01
The right software limit switch was
approached
02
The left software limit switch was
approached
Error
code
Error message Sub
error
code
Possible reason for error
Error response
(P = programma-
ble,
D = default
response)
Final error
status /
Reset type
Save
as
History
Message
binary out-
puts (valid
for default
response)