Mechanical installation
Installation
Minimum clear-
ance and mount-
ing position
• Leave
100 mm (4 in) clearance at the top and bottom
for optimum cooling. Make
sure air circulation in the clearance is not impaired by cables or other installation
equipment.
•
Ensure unobstructed cooling air supply and make sure that air heated by other
units cannot be drawn in or reused.
• Units within an axis system must be lined up without space in between.
• Only install the units
vertically
. You must not install them horizontally, tilted or upside
down.
55481BXX
Figure 42: Minimum clearance and mounting position of the units
min. 100 mm
(4 in)
min. 100 mm
(4 in)
STOP
Special bending spaces are required according to EN 61800-5-1 for cables with a cross
section of 10 mm
2
and larger. This means the clearance must be increased if required.