12
Service
Error diagnostics
Manual – MOVISAFE
®
CS..A Safety Card
100
12.5.2
Diagnostics with MOVISUITE
®
Assist CS..
The current error of the safety card is displayed with the corresponding error descrip-
tion in the "Diagnostics" segment in the menu command [MOVISAFE
®
CS..] > [Error
status].
21877778571
12.5.3
Diagnostics with PROFIsafe connection
The CS..A safety card with PROFIsafe connection triggers a diagnostic alarm at the F-
host in the data exchange between the F-host (fieldbus master) and the safety card
(fieldbus slave) in the case of an error. Simultaneously, the associated error code is
transferred via the communication connection.
The F-host responds to the dispatched diagnostic alarm if the
Diagnostic alarm as-
sembly parameter
is enabled for the safety card in the F-host per configuration. De-
pending on the fieldbus used (PROFIBUS DP or PROFINET IO), the error code of the
safety card can be evaluated in the F-host. A diagnostic alarm does not trigger an
error response in the F-host (default setting of the safety card in the F-host).
The safety card has PROFIsafe and assembly-specific error codes. All error codes of
the CS..A safety card are listed in an error table.
INFORMATION
You can find the structure and the evaluation of a diagnostic data set in the F-host in
the respective manual of the fieldbus master. In addition, ensure that the current
device description file of the SEW_EURODRIVE drive system is always installed in
the engineering tool of the F-host during configuration.
24842532/EN – 04/2018