10
Data exchange with higher-level controller
F process input data
Manual – MOVISAFE
®
CS..A Safety Card
80
10.4.2
CSB31A profile design "Technology Bus F-DO"
Byte Bit Name
Valu
e
Description
0
0
STO1
0
The STO drive safety function is not active. The
24 V supply voltage is switched on, and safe dis-
connection for the connected drive is not effective
or an error has occurred at the output.
1
The STO drive safety function reports the status
"STO active", and all outputs parameterized to
STO are without voltage.
1
Reserve
2
Reserve
3
Reserve
4
Reserve
5
Reserve
6
Warning
0
The safety card is in error-free operation.
1
At least one warning is active in the safety card.
7
Error state
0
The safety card is in error-free operation.
1
At least one warning is active in the safety card.
1
0
F-DI00
0
Process value of digital safe digital input F-DI00,
no voltage or error is present.
1
Process value of digital, safe digital input F-DI00,
voltage is present.
1
F-DI01
0
Process value of digital safe digital input F-DI01,
no voltage or error is present.
1
Process value of digital, safe digital input F-DI01,
voltage is present.
2
F-DI02
0
Process value of digital safe digital input F-DI02,
no voltage or error is present.
1
Process value of digital, safe digital input F-DI02,
voltage is present.
3
F-DI03
0
Process value of digital safe digital input F-DI03,
no voltage or error is present.
1
Process value of digital, safe digital input F-DI03,
voltage is present.
4
Reserve
5
Reserve
6
Reserve
7
Reserve
24842532/EN – 04/2018