Manual – MOVIDRIVE® MDX60B/61B Communication and Fieldbus Unit Profile
71
6
Parameters for configuring communication via fieldbus option
Fieldbus Interfaces via Option Card for MOVIDRIVE® B
6.2
Parameters for configuring communication via fieldbus option
The following parameters are used for configuring the communication in addition to the
DIP switches on the fieldbus option cards. The factory setting of the individual
parameters is underlined.
TIP
Using parameters P090 - P099 you can monitor process data and settings that are
chosen by means of the setpoint source set in P100 and P101.
Parameter
No. Name
Setting
Meaning
100
Setpoint source
TERMINALS
RS485
FIELDBUS
SBus
This parameter is used to set the setpoint
source for the inverter.
101
Control signal source
TERMINALS
RS485
FIELDBUS
SBus
This parameter is used to set the source of the
control signals for the inverter (CONTROLLER
INHIBIT, ENABLE, CW, CCW, ...). Control via
IPOS
plus®
and terminal is taken into account
disregarding of P101.
780
IP address
000.000.000.000 -
192.168.10.x -
223.255.255.255
Use P780 to set the IP address for linking
MOVIDRIVE
®
B via Ethernet. If the DHCP is
activated using P785, the value specified by
the DHCP server will be displayed.
781
Subnetwork mask
000.000.000.000 -
255.255.255.0 -
255.255.255.255
Factory setting at delivery is a class C network.
The subnetwork mask divides the network into
subnetworks. The set bits determine which part
of the IP address represents the address of the
subnetwork. If DHCP is activated, the value
specified by the DHCP server will be displayed.
782
Standard gateway
000.000.000.000 -
255.255.255.255
The standard gateway is addressed if the
desired communication partner is not within the
actual network. The standard gateway will have
to be part of the actual network. If DHCP is acti-
vated, the value specified by the DHCP server
will be displayed.
783
Baud rate
-
Display value, cannot be altered. Shows the
current baud rate of the Ethernet connection.
The value "0" is displayed during the initializa-
tion phase.
784
MAC address
-
Display value, cannot be altered. Indicates the
MAC address, i.e. the layer 2 Ethernet address
of the interface, that is clearly assigned world-
wide.
785
DHCP / Startup configuration
DHCP / Saved param-
eters
•
DHCP: The option is assigned its IP
parameters (P780 - P782) by a DHCP
server when the supply voltage is switched
on.
•
Saved IP parameters: The option is started
with the saved IP parameters when the
supply voltage is switched on.
Summary of Contents for MOVIDRIVE MDX60B