Manual – MOVIDRIVE® MDX60B/61B Communication and Fieldbus Unit Profile
6
Parameters for configuring communication via fieldbus option
Fieldbus Interfaces via Option Card for MOVIDRIVE® B
819
Fieldbus timeout interval
0 - 0.5 - 650 s
P819 sets the monitoring time for data trans-
mission via the implemented fieldbus (DFx).
MOVIDRIVE
®
B performs the error response
set in P831 Response FIELDBUS TIMEOUT if
there is no data traffic via the fieldbus for the
period set in P819. When P819 is set to the
value 0 or 650, data transmission via the field-
bus is not monitored. The timeout interval is
automatically specified by the master except
for Modbus/TCP. Changing this parameter
does not have any effect.
831
Fieldbus timeout response
RAPID STOP/WARN.
The error is only triggered in the ENABLED
inverter status. P831 programs the error
response which is triggered by the fieldbus
timeout monitoring.
870
871
872
Setpoint description PO1
Setpoint description PO2
Setpoint description PO3
Factory set to:
CONTROL WORD 1
SPEED
NO FUNCTION
P870/P871/P872 define the content of the
process output data words PO1/PO2/PO3.
873
874
875
876
Actual value description PI1
Actual value description PI2
Actual value description PI3
Enable PO data
Factory set to:
STATUS WORD 1
SPEED
NO FUNCTION
ON
The content of process input data words
PI1/PI2/PI3 is defined.
887
Synchronization ext.
controller
On/off
By default, the time base of MOVIDRIVE
®
units
is slightly smaller than 1 ms. For synchroniza-
tion with an external controller, the time base
can be set to exactly 1 ms.
888
Synchronization time
1 - 5 - 10 s
Cycle time for new setpoints of a master
control.
See also P885 Synchronization ID SBus 1 /
P895 Synchronization ID SBus 2 / P887 Syn-
chronization ext. controller and P970 DPRAM
synchronization.
970
DPRAM synchronization
On/off
MOVIDRIVE
®
B allows for synchronized opera-
tion with option cards (e.g. DHP11B, DFE24B).
ON: Synchronized operation with option card is
activated.
Important:
The inverters may either be syn-
chronized by SBus1, SBus2 or by DPRAM. The
inverters must
not be synchronized from
interfaces at the same time
. SEW-
EURODRIVE recommends to set P885/895 to
an identifier that is not used in the entire CAN
network. You need parameters P888 and P916
to implement synchronization with interpolating
setpoint processing.
OFF: Synchronized operation with the option
card is not activated.
971
Synchronization phase
(-2) - 0 - 2 s
Time interval between clock signal and data
transfer
Parameter
No. Name
Setting
Meaning