Manual – MOVIDRIVE® MDX60B/61B Communication and Fieldbus Unit Profile
95
7
Sequence control
SEW Unit Profile
7.4.8
Status word 2
Status word 2 contains both the status information in the basis status block and the
virtual output terminals DO10 - DO17 in the higher-level byte. By programming the
terminal functions for the output terminals, all the conventional signals can be processed
via the fieldbus system.
Bit Function
Definition
0
Output stage enabled
Fixed definition
1
Inverter ready
2
PO data enabled
3
Current ramp generator set
4
Current parameter set
5
Fault/warning
6
Limit switch CW active
7
Limit switch CCW active
8
Virtual terminal 1 = P630 / Binary output DO10
Virtual output terminals
9
Virtual terminal 2 = P631 / Binary output DO11
10
Virtual terminal 3 = P632 / Binary output DO12
11
Virtual terminal 4 = P633 / Binary output DO13
12
Virtual terminal 5 = P634 / Binary output DO14
13
Virtual terminal 6 = P635 / Binary output DO15
14
Virtual terminal 7 = P636 / Binary output DO16
15
Virtual terminal 8 = P637 / Binary output DO17
NOTICE
If both the fieldbus option card and DIO11 are inserted in the drive inverter, the inputs
of the DIO11 option have priority. In this case, the virtual inputs are not evaluated.