Manual – MOVIDRIVE® MDX61B Synchronous Operation Board DRS11B
31
6
Parameter descriptions
Parameter
The angular offset is then reduced to zero.
•
Mode 5: Free-running limited by
P224 Slave counter
, new reference point
– Free-running is activated via a "1" signal (>100 ms) at X40:1.
– The input terminals and setpoints of the slave drive are effective during free-
running.
– Free-running ends when the angle differential entered in P224 has been reached.
– If another HIGH signal is applied at X40:1 before free-running has ended, the
value at which free-running is to end increases to the value entered in P224.
– The slave drive synchronizes with the new angle differential.
•
Mode 6: Temporary angular offset, new reference point
– Free-running is active when a "1" signal is set at X40:1.
– The input terminals and setpoints of the slave drive are effective in free-running
mode.
– An angular offset generated in free-running mode is not processed when
synchronization is started again.
– A "1" signal at 40:2, X40:3 or X40:4 on DRS11B activates an angular offset. Each
angular offset is stored in parameters P225, P226 and P227.
– If a "0" signal is applied again at one of the input terminals X40:2, X40:3 or X40:4,
the angular offset is eliminated again.
•
Mode 7: Permanent angular offset (phase trimming), new reference point
– Free-running is active when a "1" signal is set at X40:1.
– The input terminals and setpoints of the slave drive are effective in free-running
mode.
– An angular offset generated in free-running mode is not processed when
synchronization is started again.
– A "1" signal at 40:2, X40:3 or X40:4 on DRS11B activates an angular offset. Each
angular offset is stored in parameters P225, P226 and P227.
– If a "0" signal is applied again at one of the input terminals X40:2, X40:3 or X40:4,
the angular offset is maintained.
– If the input signal lasts longer than 3 seconds, the value is corrected at four steps
per second.
•
Mode 8: Free-running unlimited, new reference point + P224
– Free-running is active when a "1" signal is set at X40:1.
– The input terminals and setpoints of the slave drive are effective in free-running
mode.
– If a "0" signal is applied at input terminal X40:1, the slave drive synchronizes with
the current position of the master drive plus the position offset stored in P224.
They must activate an offset only if a previous angular offset has been processed.
P6..
P60.
P600