106
Operating Instructions – MOVIFIT® FDC
9
Electronics data
Technical Data
9.3
Electronics data
Electronics data
DC 24 V supply
24V_C (continuous)
V
IN
= DC 24 V -15% / +20% according to EN 61131-2
Current consumption:
I
E
≤
500 mA, typically 200 mA (for MOVIFIT
®
electronics)
•
plus up to 2000 mA (4 outputs with 500 mA each)
•
plus up to 1400 mA (for sensor supply depending on the number and type of connected
sensors)
Sensor supply X25
2 circuits
•
Total current terminals 30 – 33: 700 mA
•
Total current terminals 34 – 37: 700 mA
Electrical isolation
Separate potentials for:
•
Fieldbus connection (X30, X31 internal or X11, X12 external)
•
24V_C for:
–
MOVIFIT
®
electronics including USB interface
–
DI00 – DI15
–
SBus interface
–
RS485 interface
–
24 V outputs for sensors
Shielding of bus cables
using EMC metal cable glands and fittings, and with EMC shield clamp (see operating
instructions, chapter "Installation instructions")
P
i
f
kVA
Hz
n