Operating Instructions – MOVIFIT® FDC
109
9
Interfaces
Technical Data
9.5.5
Ethernet fieldbus interface
One of the following protocols can be used for communication via the Ethernet fieldbus
interface (depending on DIP switch S12/2):
PROFINET interface
EtherNet/IP fieldbus interface
Modbus/TCP interface
PROFINET
PROFINET protocol option
PROFINET IO RT
Supported baud rates
100 Mbit/s (full duplex)
SEW ID number
010A
hex
Device ID number
2
Connection technology
2 x M12, 2 x RJ45 (push-pull) or 2 x RJ45 plug connector (in the ABOX)
Integrated switch
Supports auto-crossing, auto-negotiation
Permitted cable types
Category 5 and higher, class D according to IEC 11801
Maximum line length
(from switch to switch)
100 m according to IEEE 802.3
GSD file name
GSDML-V2.1-SEW-MOVIFIT_FDC-20100401.xml
Bitmap file name
SEW-MOVIFIT-FDC.bmp
EtherNet/IP
Automatic baud rate detection
10 MBd / 100 MBd
Connection technology
2 x M12, 2 x RJ45 (push-pull) or 2 x RJ45 plug connector (in the ABOX)
Integrated switch
Supports auto-crossing, auto-negotiation
Maximum line length
100 m according to IEEE 802.3
Addressing
4 byte IP address or MAC ID (00-0F-69-xx-xx-xx)
configurable via DHCP server or MOVITOOLS
®
MotionStudio version 5.5 and higher,
default address 192.168.10.4 (depending on the setting of DIP switch S12/1)
Manufacturer ID (vendor ID)
013B
hex
Name of EDS files
SEW_MOVIFIT_FDC.eds
Name of icon files
SEW_MOVIFIT_FDC.ico
Modbus/TCP
Automatic baud rate detection
10 MBd / 100 MBd
Connection technology
2 x M12, 2 x RJ45 (push-pull) or 2 x RJ45 plug connector (in the ABOX)
Integrated switch
Supports auto-crossing, auto-negotiation
Maximum line length
100 m according to IEEE 802.3
Addressing
4 byte IP address or MAC ID (00-0F-69-xx-xx-xx)
configurable via DHCP server or MOVITOOLS
®
MotionStudio version 5.5 and higher,
default address 192.168.10.4 (depending on the setting of DIP switch S12/1)
Supported services
FC3, FC16, FC23, FC43