46
Operating Instructions – MOVIFIT® FDC
5
Installation topologies
Electrical Installation
5.4
Installation topologies
5.4.1
Installation topology SNI (example)
The following figure shows the basic installation topology of MOVIFIT
®
FDC in conjunc-
tion with MOVIGEAR
®
SNI and DRC-SNI drive units:
18014401517353867
[1] Max. 10 x drive units (MOVIGEAR
®
SNI or DRC-SNI) in total
[2] Permitted cable length between MOVIFIT
®
and last drive unit max. 100 m
[3] Looping through the communication, the power supply and the 24 V supply is only permitted
when using the standard ABOX MTA...-S04-... Looping through is in preparation for ABOXes
MTA...-S54-.. and MTA...-S64-...
Control cabinet level
Field level
Communication
Communication [3]
Power
24 V
Power [3]
24 V [3]
Power
24 V
Single Line Installation [2]
[1]
MOVIGEAR
®
SNI
MOVIGEAR
®
SNI
DRC-SNI
MOVIFIT FDC
®
Controller
Line
filter
Pre-fuse /
line protection