Operating Instructions – MOVIFIT® FDC
53
5
Standard ABOX "MTA...-S04.-...-00"
Electrical Installation
Connecting the
hybrid cable with
CAN bus
• SEW-EURODRIVE recommends using the appropriately stripped and prefabricated
hybrid cables specifically designed for connecting MOVIFIT
®
FDC with the SBus ac-
tuators (MOVIGEAR
®
DSC or DRC-DSC).
• The outer cable shield of the hybrid cable must be applied to the MOVIFIT
®
ABOX
as follows using an EMC cable gland:
• The inner cable shield of the CAN cable in the hybrid cable must be applied to the
shield plate of the MOVIFIT
®
ABOX as follows using a clamp:
NOTICE
Damage due to missing or incorrectly mounted rubber grommet
Damage to the CAN cable
• During installation, make sure the CAN cable is protected with a rubber grommet
where it passes through the shield plate (see above figure).
• Push the CAN cable with the rubber grommet in the recess of the shield plate entirely
to the back and then slightly downward.
5595708811
1 2 3 4
9 10
23