5
Electrical installation
Hybrid cables
Operating Instructions – MOVIFIT
®
MC
110
With plug connector (MOVIFIT
®
side) and open cable end (MOVIMOT
®
side)
The table shows the assignment of the following hybrid cables:
Part number:
18145213
18145892
Hybrid cable
Terminal
Wire color/label
MOVIMOT
®
Green-yellow
PE terminal
Black/1
L1
Black/2
L2
Black/3
L3
Red/24V
24 V
White/0V
⍊
Orange/RS+
RS+
Green/RS-
RS-
White/0V
⍊
Shield end
The inner shield is connected to the
housing of the MOVIMOT
®
inverter via
the PE terminal and the overall shield is
connected via an EMC cable gland.
Note the enabled direction of rotation
Check to see if the required direction of rotation has been enabled on MOVIMOT
®
.
R
X6: 11,12
L
X6: 9,10
24V X6: 1,2,3
Both directions of rotation
are enabled.
R
X6: 11,12
L
X6: 9,10
24V X6: 1,2,3
Only CCW direction of rota-
tion is enabled.
Setpoint selections for CW
direction of rotation cause
the drive to stop.
R
X6: 11,12
L
X6: 9,10
24V X6: 1,2,3
Only CW direction of rota-
tion is enabled.
Setpoint selections for
CCW direction of rotation
cause the drive to stop.
R
X6: 11,12
L
X6: 9,10
24V X6: 1,2,3
Drive is blocked or brought
to a stop.
19484828/EN – 01/2015