6
Startup
MOVIMOT® startup
Operating Instructions – MOVIFIT
®
MC
120
Function
Setting
Detent position
0
1
2
3
4
5
6
7
8
9
10
Ramp time t1 [s]
0.1 0.2 0.3 0.5 0.7
1
2
3
5
7
10
8. Check to see if the requested direction of rotation has been enabled.
CW/Stop
CCW/Stop
Meaning
Activated
Activated
• Both directions of rotation are enabled.
R
X6: 11,12
L
X6: 9,10
24V X6: 1,2,3
Activated
Not activated • Only CW rotation is enabled.
• Setpoint selections for CCW direction of rotation
cause the drive to stop.
R
X6: 11,12
L
X6: 9,10
24V X6: 1,2,3
Not activated
Activated
• Only CCW rotation is enabled
• Setpoint selections for CW direction of rotation
cause the drive to stop.
R
X6: 11,12
L
X6: 9,10
24V X6: 1,2,3
Not activated
Not activated • Unit is blocked or drive is brought to a stop
R
X6: 11,12
L
X6: 9,10
24V X6: 1,2,3
9. Place the MOVIMOT
®
inverter onto the connection box and screw it on tightly.
3
4
5
6
7
8
19484828/EN – 01/2015