7
Operation
MOVIFIT® MC status LEDs
Operating Instructions – MOVIFIT
®
MC
129
"RUN" LED
The following table shows the statuses of the "RUN" LED:
LED
Meaning
Measure
Off
MOVIFIT
®
not ready for opera-
tion.
No 24 V power supply.
• Check DC 24 V supply.
• Switch on MOVIFIT
®
again. Ex-
change EBOX if problem occurs
repeatedly.
Green
Illuminated
MOVIFIT
®
assembly hardware
OK.
-
Green
Illuminated
If "BUS-F" LED is off:
MOVIFIT
®
operating correctly.
MOVIFIT
®
is currently exchanging
data with the DP master and all
subordinate drive systems.
-
Green
Flashing
PROFIBUS address is set equal
to 0 or higher than 125.
Check the PROFIBUS address that
is set in the MOVIFIT
®
ABOX.
Yellow
Illuminated
MOVIFIT
®
is in the initialization
phase.
-
Red
Illuminated
Internal unit fault
Switch on MOVIFIT
®
again. Ex-
change EBOX if problem occurs re-
peatedly.
19484828/EN – 01/2015