5
Electrical installation
Standard ABOX "MTA...-S01.-...-00"
Operating Instructions – MOVIFIT
®
MC
58
X29: 24 V distributor terminals
WARNING
Danger due to unexpected unit behavior When you use terminals X29/5 and X29/6
for the safe disconnection function, you must observe the SEW manual
"MOVIFIT
®
MC/FC – Functional Safety".
Severe or fatal injuries may result.
• Note the permitted wiring diagrams and the safety conditions in the
"MOVIFIT
®
MC/FC – Functional Safety" manual.
X20
1
11 12 13 14 15 16
2
3
4
5
6
1
2
3
4
11 12 13 14
X1
S3
1
1 2 3 4 5
11
1 2 3 4 5
12 13 14 15
11
1 2 3 4 5
12 13 14 15
31 32 33 34 35
21 22 23 24 25
11
1 2 3 4 5 6 7 8
12 13 14 15 16 17 18
31 32 33 34 35 36 37 38
21 22 23 24 25 26 27 28
2
3
4
1
2
3
4
X71
X45
X25
X35
X50
1 2 3 4 5
X81
1 2 3 4 5
X91
X7
1
2
3
4
X8
X9
1
11 12 13 1415 16
2 3 4 5 6
1718
7 8
X29
1020352011
24 V distributor terminal (for distributing the supply voltage(s) to the MOVIMOT
®
units and the option card)
No.
Name
Function
X29
1
+24V_C
+24 V supply – continuous voltage (jumpered with X20/2)
2
0V24_C
0V24 reference potential – continuous voltage (jumpered with X20/3)
3
+24V_S
+24 V supply – switched (jumpered with X20/5)
4
0V24_S
0V24 reference potential – switched (jumpered with X20/6)
5
+24V_P
+24 V supply for MOVIMOT
®
(IN)
6
0V24_P
0V24 reference potential for MOVIMOT
®
(IN)
7
+24V_O
+24 V supply for option card, supply
8
0V24_O
0V24 reference potential for option card, supply
11
+24V_C
+24 V supply – continuous voltage (jumpered with X20/2)
12
0V24_C
0V24 reference potential – continuous voltage (jumpered with X20/3)
13
+24V_S
+24 V supply – switched (jumpered with X20/5)
14
0V24_S
0V24 reference potential – switched (jumpered with X20/6)
15
+24V_P
+24 V supply for MOVIMOT
®
(OUT)
16
0V24_P
0V24 reference potential for MOVIMOT
®
(OUT)
17
+24V_O
+24 V supply for option card, supply
18
0V24_O
0V24 reference potential for option card, supply
INFORMATION
• The terminal assignment "X29" illustrated here applies as of status 11 of the wir-
ing board. If you use a wiring board with another status, consult
SEW
‑
EURODRIVE. The status of the wiring board is indicated in the first status
field of the ABOX nameplate:
Status: 11 11 -- 10 -- 10 10 -- --
Status of the wiring board
19484828/EN – 01/2015