6
Startup
Startup of MOVIFIT® on the fieldbus
Operating Instructions – MOVIFIT
®
MC
124
6.6.3
Startup with DeviceNet™
1. Check the MOVIFIT
®
connection.
2. Set the DeviceNet™ address at DIP switch S2 of the ABOX.
3. Set the baud rate at DIP switch S2 of the ABOX.
4. Start up the MOVIFIT
®
inverter, see chapter "Startup of the MOVIFIT
®
frequency in-
verter".
5. Place the EBOX onto the ABOX and close it.
6. Switch on the 24V_C and 24V_S supply voltage(s). The corresponding control
LEDs should now light up green.
Setting DeviceNet™ address (MAC ID) and baud rate
The DeviceNet™ address is set with DIP switches S2/1 to S2/6.
The Baud rate is set with DIP switches S2/7 to S2/8:
S2
2
0
x 1 = 1
2
1
x 0 = 0
2
2
x 0 = 0
2
4
x 0 = 0
2
3
x 1 = 8
2
5
x 0 = 0
2
1
x 1 = 2
2
0
x 0 = 0
9
[1]
2
[2]
ON
1
2
3
4
5
6
7
8
9007200092311435
[1] Setting the DeviceNet™ address
[2] Setting the baud rate
In the following table, address 9 is used as an example to show how to set any bus
address at the DIP switches:
DIP switch
Switch position
Significance
S2/1
ON
1
S2/2
OFF
2
S2/3
OFF
4
S2/4
ON
8
S2/5
OFF
16
S2/6
OFF
32
The following table shows how to set the baud rate at the DIP switches:
Baud rate
Value
S2/7
S2/8
125 kBd
0
OFF
OFF
250 kBd
1
ON
OFF
500 kBd
2
OFF
ON
(reserved)
3
ON
ON
19484828/EN – 01/2015