9
Technical data
Digital inputs
Operating Instructions – MOVIFIT
®
MC
149
9.4
Digital inputs
Digital inputs
Function level "Classic" with
PROFIBUS or DeviceNet™
Function level "Technology" with
PROFIBUS
Function level "Classic" or "Tech-
nology" with PROFINET IO, Ether-
Net/IP™, or Modbus/TCP
Number of inputs
6 – 8
12 – 16
Input type
PLC-compatible according to EN 61131
‑
2 (digital inputs type 1)
R
i
about 4 kΩ, sampling cycle ≤ 5 ms
Signal level:
+15 V – +30 V
-3 V – +5 V
"1" = contact closed
"0" = contact open
Number of simultaneously
controllable inputs
8
16 at 24 V
8 at 28.8 V
Sensor supply
(4 groups)
DC 24 V to EN 61131-2, interference voltage proof and short-circuit-proof
Rated current
Permitted total current
Internal voltage drop
500 mA per group
2 A / 1 A at ambient temperatures above 30 °C
max. 2 V
Potential reference
Group III
Group IV
→ 24V_C
→ 24V_S
9.5
Digital outputs DO00 – DO03
Digital outputs
Function level "Classic" with
PROFIBUS or DeviceNet™
Function level "Technology" with
PROFIBUS
Function level "Classic" or "Tech-
nology" with PROFINET IO, Ether-
Net/IP™, or Modbus/TCP
Number of outputs
0 – 2
0 – 4
Output type
PLC-compatible to EN 61131-2, interference voltage proof and short-cir-
cuit-proof
Rated current
Permitted total current
Leakage current
Internal voltage drop
500 mA
2 A / 1 A at ambient temperatures above 30 °C
max. 0.2 mA
max. 2 V
Potential reference
24V_S
19484828/EN – 01/2015