5
Electrical installation
Electrical connections
Operating Instructions – MOVIFIT
®
MC
91
5.11.7
X11: DeviceNet™ interface
The following table shows information about this connection:
Function
DeviceNet™ interface
Connection type
(Micro-style connector, male, A
‑
coded)
Wiring diagram
2
1
5
4
3
9007201519559179
Assignment
No.
Name
Function
1
Drain
Shield/equipotential bonding
2
V+
DC 24 V input
3
V-
Reference potential
4
CAN_H
CAN data line (high)
5
CAN_L
CAN data line (low)
19484828/EN – 01/2015