Electrical installation
Fieldbus systems connection examples
Operating Instructions – MOVIFIT
®
MC
99
5.14.2
PROFIBUS via M12 plug connectors
INFORMATION
This example is valid for ABOXes with PROFIBUS plug connectors.
The following figure shows the basic connection topology for PROFIBUS via M12 plug
connectors:
• For the PROFIBUS connection, the ABOXes have M12 plug connectors. They
comply with the recommendations of PROFIBUS directive no. 2.141 "Connection
technology for PROFIBUS".
• To prevent malfunctions in the bus system due to reflections, etc., the PROFIBUS
segment must be terminated using bus terminating resistors at the first and last
stations.
• The bus terminating resistors are already installed in the MOVIFIT
®
ABOX and they
can be activated using the S1 switch.
MOVIFIT
®
MOVIFIT
®
MOVIFIT
®
PROFIBUS DP
[1]
S1
[2]
ON
9007200067225483
[1] Bus terminating resistor on the controller
[2] S1 DIP switch = "ON" for bus termination
19484828/EN – 01/2015