Communication and unit profile
Startup
Fault/warning
With bit 5 in the status word, the inverter signals a possible fault or warning. The result
of a
fault
is always that the frequency inverter is no longer ready for operation. A
warn-
ing
can occur temporarily without affecting the operating behavior of the inverter. This
is why you should also evaluate status bit 1
inverter ready
to exactly filter a fault (require-
ment: line voltage ON).
Status word 1
Status word 1 contains the status information in the basic status block and the
unit status
or the
fault number
in the higher-level status byte. The unit status is displayed when fault
bit = 0, and the fault number is displayed in case of a fault (fault bit = 1). The fault bit is
reset by resetting the fault, and the current unit status is displayed again. You find infor-
mation on the meaning of the fault numbers and the device status in the system manual
or in the MOVITRAC
®
B operating instructions.
Bit 1: Ready
Bit 5: Fault/warning
Meaning
0
0
Inverter not ready for operation
0
1
Fault
1
0
Inverter is ready for operation
1
1
Warning
Bit Function
Definition
0
Output stage enabled
Fixed definition
1
Inverter ready
2
PO data enabled
3
Current ramp generator set
4
Current parameter set
5
Fault/warning
6
Reserved
7
Reserved
8
Fault/warning?
Bit 5 = 1
→
fault number:
01 Overcurrent
02 ...
Bit 5 = 0
→
unit status:
0x1 Controller inhibit
0x2 ...
Unit status / fault number
9
10
11
12
13
14
15
00
I