104
Operating Instructions – MOVITRAC® B
5
Communication and unit profile
Startup
5.11.5 Monitoring functions
For safe operation of the MOVITRAC
®
frequency inverter via communication interfaces,
additional monitoring functions have been implemented that trigger an operator-defined
drive function in the event of a bus fault. Two individual parameters are available for
each communication interface.
• Timeout interval
• Timeout response
This parameter defines an application-specific drive behavior in case of a communica-
tion error.
Timeout error mes-
sage / timeout
interval / timeout
response
The frequency inverter generates a timeout if no new data is received via the bus system
within a preset time frame (timeout interval). The timeout response can be set and de-
fines the malfunction (fault/warning) and the fault response of the drive.
Timeout error mes-
sage
MOVITRAC
®
B generates a separate
timeout error message for every communica-
tion interface
:
Timeout interval
The
timeout interval
can be set individually for each communication interface.
Timeout response
The
timeout response
can be set individually for each communication interface.
Communication interface
Fault number
Timeout error message
RS485
F 43
RS485 TIMEOUT
SBus
F 47
SBUS 1 TIMEOUT
Communication interface
Parameter number
Parameter name
Timeout interval
RS485
812
RS485 timeout interval
0.00 seconds
SBus
883
SBus 1 timeout interval
0.10 seconds
Parameter number
Parameter name
Timeout response
833
Response RS485 TIMEOUT
RAPID STOP/WARN.
836
Response to SBus1 TIMEOUT
RAPID STOP/WARN.
00