Status displays
Operation
Cause for control-
ler inhibit (OFF)
Controller inhibit (OFF) can be caused by the following conditions:
• Digital input terminal set to controller inhibit and active.
• Controller inhibit due to PC manual mode via MOVITOOLS
®
MotionStudio.
• Temporary controller inhibit: Is triggered if a change of parameter
P100 setpoint
source
would directly cause an enable signal. The temporary controller inhibit is re-
moved once the enable signal is reset for the first time.
• Controller inhibit set via IPOS
®
control word H484.
6.2.2
Status of digital inputs / outputs
The following parameters are available in the parameter menu as display parameters:
•
P039 Digital inputs of basic unit
•
P048 Digital inputs option
•
P059 Digital outputs
The status is displayed as binary. Every digital input or output has two segments verti-
cally on top of one another of the 7-segment display assigned to it. The upper segment
lights up when the digital input or output is set, and the lower segment lights up when
the digital input or output is not set. The two 7-segment displays on the right indicate
whether
P039
(di = digital inputs basic unit),
P048
(dI = digital inputs option), or
P059
(do = digital outputs) are output.
If no FIO21B with digital inputs is available, the display will show
dl - - -
.