184
Operating Instructions – MOVITRAC® B
8
Technical data for accessories and options
Technical data
FSC11B communication module
Part number: 1820 716 2
Description
The FSC11B communication module provides the MOVITRAC
®
B communication inter-
faces to the outside, for communication with PLC, MOVITRAC
®
B, MOVIDRIVE
®
, PC or
operator panel. The following interfaces are available:
• RS485
• CAN-based system bus (SBus) (supported protocols: MOVILINK
®
/ CANopen)
Electronics data for FSC11B communication module
The terminal cross-section for all terminals of the FSC11B is:
• 1.5 mm
2
(AWG15) without conductor end sleeves
• 1.0 mm
2
(AWG17) with conductor end sleeves
235261451
X45
X46
1 2 3 4 5 6
H L
⊥
FSC11B
7
X44
S1
S2
OFF
ON
Function
Terminal
Designation
Data
System bus
(SBus)
X46:1
X46:2
X46:3
X46:4
X46:5
X46:6
X46:7
SC11: SBus high
SC12: SBus low
GND: Reference potential
SC21: SBus high
SC22: SBus low
GND: Reference potential
24VIO: Auxiliary voltage /
External voltage supply
CAN bus according to CAN specification 2.0, parts A and B, transmis-
sion technology according to ISO 11898, max. 64 stations, terminating
resistor (120
Ω
) can be activated using DIP switch
S1
.
Service inter-
face
X44
RJ10
Service interface
EIA standard, 9.6 kBd
Connection: Only for service purposes, solely for point-to-point
connection
Maximum cable length 3 m (10 ft)
RS485 inter-
face
X45:H
X45:L
X45:
⬜
ST11: RS485+
ST12: RS485–
GND: Reference potential
EIA standard, 9.6 kBd, max. 32 stations
Maximum cable length 200 m (656 ft)
Dynamic terminating resistor with fixed installation
P
i
f
kVA
Hz
n