186
Operating Instructions – MOVITRAC® B
8
Technical data for accessories and options
Technical data
Electronics data for FSC12B communication module
Terminal cross-section for all terminals of the FSC12B:
• 1.5 mm
2
(AWG15) without conductor end sleeves
• 1.0 mm
2
(AWG17) with conductor end sleeves
All DIP switches are set to OFF by default. This means the values set in parameter
P88.
apply.
If no or several baud rates are selected via DIP switches S1:2 – S1:5, the baud rate set
in parameter
P884
applies.
If an invalid address is set via DIP switch S2, the addresses set in
P881
and
P886
apply.
Examples of invalid addresses:
• Address > 63 in the MOVILINK
®
profile (S1:1 = OFF) or
• Address > 127 or address = 0 in the CANopen profile (S1:1 = ON)
The FSC12B is only supported as of MOVITRAC
®
firmware 1822 5632.
11
.
Older firmware versions do not allow for communication via CAN.
SEW-EURODRIVE recommends that you use MOVITOOLS
®
MotionStudio version
5.80 or later.
Function
Terminal/
switch
Designation
Data
System bus
(SBus)
X46:1
X46:2
X46:3
X46:4
X46:5
X46:6
X46:7
SC11: SBus high
SC12: SBus low
GND: Reference potential
SC11: SBus high
SC12: SBus low
GND: Reference potential
24VIO: Auxiliary voltage /
External voltage supply
CAN bus according to CAN specification 2.0, parts A and B, transmis-
sion technology according to ISO 11898, max. 64 stations, terminating
resistor (120
Ω
) can be activated using DIP switch
S1:8
(back).
Service inter-
face
X44
RJ10
Service interface
EIA standard, 9.6 kBd
Connection: Only for service purposes, solely for point-to-point con-
nection
Maximum cable length 3 m (10 ft)
RS485 inter-
face
X45:H
X45:L
X45:
⬜
ST11: RS485+
ST12: RS485–
GND: Reference potential
EIA standard, 9.6 kBd, max. 32 stations
Maximum cable length 200 m (656 ft)
Dynamic terminating resistor with fixed installation
DIP switches
S2
Address
Binary coded: 1:2
0
; 2:2
1
; 3:2
2
Example: Address 9: S2:1 and S2:4 = ON
Permitted address range:
•
0 – 63 (MOVILINK
®
: S1:1 = OFF)
•
1 – 127 (CANopen: S1:1 = ON)
S1
S1:1 CAN profile
S1:2 125 kBd
S1:3 250 kBd
S1:4 500 kBd
S1:5 1 MBd
S1:6 F1
S1:7 F2
S1:8 terminating resistor
OFF = MOVILINK
®
, ON = CANopen
S1:2 – S1:5
•
Baud rate: you may select exactly 1 baud rate
S1:6 – S1:7
•
F1 and F2 are reserved and may not be activated
S1:8 switches a 120
Ω
bus termination between CAN high and
CAN low
P
i
f
kVA
Hz
n
Summary of Contents for Movitrac B
Page 2: ...SEW EURODRIVE Driving the world...