Operating Instructions – MOVITRAC® B
23
4
Installation notes for basic unit – electrical aspects
Installation
Maximum val-
ues/fuses
The following maximum values/fuses must be observed for UL compliant installation:
230 V units / 1-phase
Max. line current
Max. line voltage
Fuses
0003 / 0004 / 0005 / 0008
AC 5000 A
AC 240 V
15 A / 250 V
0011 / 0015 / 0022
AC 5000 A
AC 240 V
30 A / 250 V
230 V units / 3-phase
Max. line current
Max. line voltage
Fuses
0003 / 0004 / 0005 / 0008
AC 5000 A
AC 240 V
15 A / 250 V
0011 / 0015 / 0022
AC 5000 A
AC 240 V
20 A / 250 V
0037
AC 5000 A
AC 240 V
30 A / 250 V
0055 / 0075
AC 5000 A
AC 240 V
110 A / 250 V
0110
AC 5000 A
AC 240 V
175 A / 250 V
0150
AC 5000 A
AC 240 V
225 A / 250 V
0220 / 0300
AC 10000 A
AC 240 V
350 A / 250 V
400/500 V units
Max. line current
Max. line voltage
Fuses
0003 / 0004 / 0005 / 0008 /
0011 / 0015
AC 5000 A
AC 500 V
15 A / 600 V
0022 / 0030 / 0040
AC 5000 A
AC 500 V
20 A / 600 V
0055 / 0075
AC 5000 A
AC 500 V
60 A / 600 V
0110
AC 5000 A
AC 500 V
110 A / 600 V
0150 / 0220
AC 5000 A
AC 500 V
175 A / 600 V
0300
AC 5000 A
AC 500 V
225 A / 600 V
0370 / 0450
AC 10000 A
AC 500 V
350 A / 600 V
0550 / 0750
AC 10000 A
AC 500 V
500 A / 600 V
INFORMATION
Use only tested units with a limited output voltage (V
max
= DC 30 V) and limited output
current (I
≤
8 A) as an external DC 24 V voltage source.
UL certification does not apply to operation in voltage supply systems with a non-
grounded star point (IT systems).