Operating Instructions – MOVITRAC® B
33
4
Installing accessories and options – mechanical aspects
Installation
– Use a copper protective earth conductor with a cross section of 10 mm
2
• Supply system cable 10 – 16 mm
2
:
– Use a copper protective earth conductor with the cross section of the supply sys-
tem lead.
• Supply system cable 16 – 35 mm
2
:
– Use a copper protective earth conductor with a cross section of 16 mm
2
• Supply system lead > 35 mm
2
:
– Use a copper protective earth conductor with half the cross section of the supply
system cable.
4.2.16 Interference emission
• Use shielded motor cables or HD output chokes for EMC compliant installation.
4.2.17 Digital outputs
• The digital outputs are short-circuit proof and protected against external voltage to
30 V. Higher external voltages can destroy the digital outputs.
4.3
Installing accessories and options – mechanical aspects
4.3.1
Attaching the front modules
Attach the front modules as follows:
3889591435
1.
2.
3.
4.
FIO 11B
FIO 21B
FSC 11B
FSC 12B
FSE 24B