46
Operating Instructions – MOVITRAC® B
4
Installing accessories and options – electrical aspects
Installation
MOVITRAC
®
B system bus connection with DFx/UOH11B gateways or DFx integrated
in MOVITRAC
®
B
9007199494905355
X45
X46
1 2 3 4 5 6
H L
FSC11B / 12B
MOVITRAC
®
B
7
X44
S1
S2
OFF
ON
X26
1 2 3 4 5 6 7
UOH11B
X24
H1
H2
DFP21B
0 1
2
2
2
2
0
1
2
3
2
2
2
AS
4
5
6
X30
ADDRESS
1
6
5
9
RUN
BUS
FAULT
+ 24 V
GND
Cable length
•
The permitted total cable length depends on the baud rate setting of the SBus (
P884
):
– 125 kBd: 500 m (1640 ft)
– 250 kBd: 250 m (820 ft)
– 500 kBd: 100 m (328 ft)
– 1000 kBd: 25 m (82 ft)
•
You must use shielded cables.
INFORMATION
• Terminating resistor: Switch on the system bus terminating resistor (S1 = ON) at
the start and end of the system bus connection. Switch off the terminating resistor
on the units in between (S1 = OFF).
• Certain units have a permanently integrated terminating resistor that cannot be
switched off. This is the case for UFx and DFx/UOH. These gateways form the end
of the physical line.
Do not connect any external terminating resistors.