Operating Instructions – MOVITRAC® B
59
5
Preliminary work and resources
Startup
5.2.1
Preliminary work and tools for startup with factory setting
• Connect the supply system and the motor.
• Connect the signal terminals.
• Switch on the power supply system.
5.2.2
Preliminary work and tools for startup with keypad or with PC
• Connect the supply system and the motor.
Do not connect signal terminals to pre-
vent the inverter from receiving an enable signal!
• Switch on the power supply system.
• The display shows
Stop
.
• Program the signal terminals.
• Set the parameters (e.g. ramps).
• Check the terminal assignment that has been set (
P601
–
P622
).
• Switch off the power supply system.
• Connect the signal terminals.
• Switch on the power supply system.
INFORMATION
The inverter automatically changes parameter values once you perform a startup.