72
Operating Instructions – MOVITRAC® B
5
Keypads
Startup
Manual mode
The inverter can be controlled using the DBG60B keypad in manual mode (context
menu
→
manual mode).
The digital inputs will be without any functions for the duration of manual operation, with
the exception of a "/Controller inhibit". A digital input "/Controller inhibit" must be as-
signed a "1" signal to enable the drive to be started in manual operation.
The direction of rotation is not determined by the "CW/stop" or "CCW/stop" digital inputs.
Instead, you select the direction of rotation using the DBG60B keypad.
• Enter the required speed and then the direction of rotation (+ = CW / – = CCW) using
the sign key (+/–).
Manual operation remains active when the power supply is switched off and on; how-
ever, the inverter is then inhibited.
• Use the RUN key to enable and start the inverter at n
min
in the selected direction of
rotation. The speed is increased and decreased using the
↑
and
↓
keys.
•
DANGER
Risk of crushing if the motor starts up unintentionally.
Severe or fatal injuries.
– Ensure that the motor cannot start inadvertently, for example, by removing the
electronics terminal block X13.
– Additional safety precautions must be taken depending on the application to avoid
injury to people and damage to machinery.
INFORMATION
If you quit manual mode, the signals at the digital inputs are active immediately. A dig-
ital input / controller inhibit does not have to be wired "1"-"0"-"1". The drive can start
according to the signals at the digital inputs and the setpoint sources.
00
I
Summary of Contents for Movitrac B
Page 2: ...SEW EURODRIVE Driving the world...