128
Operating Instructions – MOVITRAC® B
6
Status displays
Operation
6.2
Status displays
6.2.1
Basic unit / FBG11B keypad
The status displays on the unit are as follows:
Saving parameter set to FBG11B
→
display u. u.
Saving parameter set to unit
→
display d. d.
•
WARNING
Incorrect interpretation of display U = "Safe stop" active
Severe or fatal injuries.
– The display U = "Safe stop" is not safety-related and must not be used as a safety
function.
Status
Display (optionally with
FBG11B keypad)
Basic unit status LED flash
code
Unit status
codes (high byte
in status word 1)
"ENABLE"
Speed
Constant green light
4
"ENABLE" at current limit
Speed flashes
Rapid green flashing
"CURRENT AT STAND-
STILL"
dc
Slow green flashing
3
"NO ENABLE"
Stop
Constant yellow light
2
"FACTORY SETTING"
SEt
Rapid yellow flashing
8
"CONTROL.INHIBIT"
oFF
Rapid yellow flashing
1
"24 V operation"
24U
Flashing
Slow yellow flashing
0
"SAFE STOP"
1)
U
flashing or
24U
flashing
Slow yellow flashing
17
FBG manual mode active or
inverter stopped using STOP
button.
FGB manual operation sym-
bol or "stop" is flashing
Yellow on long, off briefly
Timeout
Faults 43 / 47
Flashing green/yellow
Copy
Fault 97
Flashing red/yellow
System error
Faults 10 / 17 – 24 / 25 / 32 /
37 / 38 / 45 / 77 / 80 / 94
Constant red light
Overvoltage / phase failure
Faults 4 / 6 / 7
Slow red flashing
Overload
Faults 1 / 3 / 11 / 44 / 84
Rapid red flashing
Monitoring
Faults 8 / 26 / 34 / 81 / 82
2 x red flashing
Motor protection
Faults 31 / 84
3 x red flashing
1) "U" flashing (status 17) if connected to supply system, "24U" flashing (status 0) if in backup mode.