Technical data of the basic unit
Technical data
8.1.2
General technical data
The following technical data applies to all MOVITRAC
®
B frequency inverters indepen-
dent of size and power.
MOVITRAC
®
B
All sizes
Interference immunity
Meets EN 61800-3
Interference emission with
EMC-compliant installation
(Line end)
According to limit value class
1)
•
Sizes 0 to 2: C2 without further measures
•
Sizes 0 to 5: C1 with corresponding filters / folding ferrites
C1/C2 to EN 61800-3
Leakage current
> 3.5 mA
Ambient temperature
ϑ
A
(up to 60 °C with current
reduction)
•
230 V, 0.25 – 2.2 kW (0.34 – 3.0 HP) / 400/500 V, 0.25 – 4.0 kW (0.34 – 5.4 HP)
With overload capacity
(max. 150% I
N
for 60 s):
I
D
= 100% I
N
/ f
PWM
= 4 kHz: –10 °C to +40 °C
Without overload capacity:
I
D
= 100% I
N
/ f
PWM
= 4 kHz: –10 °C to +50 °C
I
D
= 100% I
N
/ f
PWM
= 8 kHz: –10 °C to +40 °C
I
D
= 125% I
N
/ f
PWM
= 4 kHz: –10 °C to +40 °C
•
3 × 230 V, 3.7 – 30 kW (5.0 – 40 HP) / 400/500 V, 5.5 – 75 kW (7.4 – 100 HP)
With overload capacity
(max. 150% I
N
for 60 s):
I
D
= 100% I
N
/ f
PWM
= 4 kHz: 0 °C to +40 °C
Without overload capacity:
I
D
= 100% I
N
/ f
PWM
= 4 kHz: 0 °C to +50 °C
I
D
= 100% I
N
/ f
PWM
= 8 kHz: 0 °C to +40 °C
I
D
= 125% I
N
/ f
PWM
= 4 kHz: 0 °C to +40 °C
•
Mounting platform with
"Cold plate"
< 70 °C
Derating ambient temperature
(current reduction)
2.5% I
N
per K at 40 °C to 50 °C
3% I
N
per K at 50 °C to 60 °C
Climate class
EN 60721-3-3, class 3K3
Storage temperature
Transport temperature
–25 °C to +75 °C
–25 °C to +75 °C
Type of cooling
Self-cooling:
230 V:
≤
0.75 kW (1.0 HP)
400/500 V:
≤
1.1 kW (1.5 HP)
Forced cooling:
230 V:
≥
1.1 kW (1.5 HP)
400/500 V:
≥
1.5 kW (3.0 HP)
(temperature-controlled fan, response threshold 45 °C)
Degree of protection
EN 60529 (NEMA 1)
Sizes 0 to 3: IP20
Sizes 4 – 5 power connections:
•
IP00
•
With the supplied Plexiglas cover mounted and shrinking tube mounted (not sup-
plied) IP10
Duty type
Continuous duty
Overvoltage category
III according to IEC 60664-1 (VDE 0110-1)
Line voltage tolerance
EN 50160: ± 10%
Pollution class
2 according to IEC 60664-1 (VDE 0110-1)
Protection against mechani-
cally active substances
3S1
Protection against chemically
active substances
3C2
Table continued on next page.
P
i
f
kVA
Hz
n