148
Operating Instructions – MOVITRAC® B
8
Technical data of the basic unit
Technical data
AC 400/500 V / 3-phase / size 0XS / 0.25 / 0.37 kW / 0.34 / 0.50 HP
The dimensions are specified in mm (in).
* With front module 4 mm (0.16 in)
MOVITRAC
®
MC07B (3-phase supply system)
0003-5A3-4-00
0004-5A3-4-00
Part number (without "safe stop")
828 515 2
828 516 0
INPUT
1)
Nominal line voltage
V
line
3 × AC 380 – 500 V
Nominal line frequency
f
line
50/60 Hz ±5%
Nominal line current
(at V
line
= 3 × AC 400 V)
I
line
I
line 125
AC 0.9 A
AC 1.1 A
AC 1.4 A
AC 1.8 A
OUTPUT
Output voltage
V
O
3 × 0 – V
line
Recommended motor power 100% operation
Recommended motor power 125% operation
P
Mot
P
Mot 125
0.25 kW / 0.34 HP
0.37 kW / 0.50 HP
0.37 kW / 0.50 HP
0.55 kW / 0.74 HP
Nominal output current 100% operation
Nominal output current 125% operation
I
N
I
N 125
AC 1.0 A
AC 1.3 A
AC 1.6 A
AC 2.0 A
Apparent output power 100% operation
Apparent output power 125% operation
S
N
S
N 125
0.7 kVA
0.9 kVA
1.1 kVA
1.4 kVA
Min. perm. braking resistance
(4-quadrant operation)
R
BW_min
68
Ω
GENERAL INFORMATION
Power loss 100% operation
Power loss 125% operation
P
V
P
V 125
30 W
35 W
35 W
40 W
Type of cooling / cooling air consumption
Natural convection / –
Current limitation
150% I
N
for at least 60 seconds
Unit terminal cross section / tightening torque
Terminals
4 mm
2
/ AWG12 / 0.6 Nm / 5 lb in
Dimensions
W × H × D
54.5 mm × 185 mm × 163.5 mm (2.15 in × 7.28 in × 6.437 in)
Mass
m
1.3 kg / 2.9 lb
1) The line and output currents must be reduced by 20% from the nominal values for V
line
= 3 × AC 500 V.
220 (8.66)
196 (7.72)
49.5 (1.95)
54.5 (2.15)
6 (0.2)
6 (0.2)
163.5 (6.437)
185 (7.28)
285 (1
1.2)
159.5 (6.280) *
149 (5.87)
P
i
f
kVA
Hz
n