Operating Instructions – MOVITRAC® B
151
8
Technical data of the basic unit
Technical data
AC 400/500 V / 3-phase / size 2S / 5.5 / 7.5 kW / 7.4 / 10 HP
* With front module 4 mm (0.16 in)
MOVITRAC
®
MC07B (3-phase supply system)
0055-5A3-4-00
0075-5A3-4-00
Part number ("Safe stop" integrated)
828 524 1
828 526 8
INPUT
1)
1) The line and output currents must be reduced by 20% from the nominal values for V
line
= 3 × AC 500 V.
Nominal line voltage
V
line
3 × AC 380 – 500 V
Nominal line frequency
f
line
50/60 Hz ±5%
Nominal line current
(at V
line
= 3 × AC 400 V)
I
line
I
line 125
AC 11.3 A
AC 14.1 A
AC 14.4 A
AC 18.0 A
OUTPUT
Output voltage
V
O
3 × 0 – V
line
Recommended motor power 100% operation
Recommended motor power 125% operation
P
Mot
P
Mot 125
5.5 kW / 7.4 HP
7.5 kW / 10 HP
7.5 kW / 10 HP
11 kW / 15 HP
Nominal output current 100% operation
Nominal output current 125% operation
I
N
I
N 125
AC 12.5 A
AC 15.6 A
AC 16 A
AC 20 A
Apparent output power 100% operation
Apparent output power 125% operation
S
N
S
N 125
8.7 kVA
10.8 kVA
11.1 kVA
13.9 kVA
Min. perm. braking resistance (4-quadrant operation)
R
BW_min
47
Ω
GENERAL INFORMATION
Power loss 100% operation
Power loss 125% operation
P
V
P
V 125
220 W
290 W
290 W
370 W
Current limitation
150% I
N
for at least 60 seconds
Type of cooling / cooling air consumption
Forced cooling / 80 m
3
/h
Unit terminal cross section / tightening torque
Terminals
4 mm
2
/ AWG12 / 0.6 Nm / 5 lb in
Dimensions
W × H × D
105 mm × 335 mm × 238 mm (4.13 in × 13.2 in × 9.37 in)
Mass
m
5.0 kg / 11 lb
7 (0.3)
325 (12.8)
105 (4.13)
70 (2.8)
238 (9.37) *
234 (9.21)
335 (13.2)
P
i
f
kVA
Hz
n
Summary of Contents for Movitrac B
Page 2: ...SEW EURODRIVE Driving the world...
Page 259: ......