152
Operating Instructions – MOVITRAC® B
8
Technical data of the basic unit
Technical data
AC 400/500 V / 3-phase / size 2 / 11 kW / 15 HP
* With front module 4 mm (0.16 in)
MOVITRAC
®
MC07B (3-phase supply system)
0110-5A3-4-00
Part number ("Safe stop" integrated)
828 527 6
INPUT
1)
1) The line and output currents must be reduced by 20% from the nominal values for V
line
= 3 × AC 500 V.
Nominal line voltage
V
line
3 × AC 380 – 500 V
Nominal line frequency
f
line
50/60 Hz ±5%
Nominal line current
(at V
line
= 3 × AC 400 V)
I
line
I
line 125
AC 21.6 A
AC 27.0 A
OUTPUT
Output voltage
V
O
3 × 0 – V
line
Recommended motor power 100% operation
Recommended motor power 125% operation
P
Mot
P
Mot 125
11 kW / 15 HP
15 kW / 20 HP
Nominal output current 100% operation
Nominal output current 125% operation
I
N
I
N 125
AC 24 A
AC 30 A
Apparent output power 100% operation
Apparent output power 125% operation
S
N
S
N 125
16.6 kVA
20.8 kVA
Min. perm. braking resistance
(4-quadrant operation)
R
BW_min
22
Ω
GENERAL INFORMATION
Power loss 100% operation
Power loss 125% operation
P
V
P
V 125
400 W
500 W
Type of cooling / cooling air consumption
Forced cooling / 80 m
3
/h
Current limitation
150% I
N
for at least 60 seconds
Unit terminal cross section / tightening torque
Terminals
4 mm
2
/ AWG12 / 0.6 Nm / 5 lb in
6 mm
2
/ AWG10 / 1.5 Nm / 13 lb in
Dimensions
W × H × D
130 mm × 335 mm × 229 mm (5.12 in × 13.2 in × 9.02 in)
Mass
m
6.6 kg / 15 lb
300 (1
1.8)
6.5 (0.26)
130 (5.12)
105 (4.13)
229 (9.02) *
225 (8.86)
335 (13.2)
315 (12.4)
P
i
f
kVA
Hz
n
Summary of Contents for Movitrac B