Operating Instructions – MOVITRAC® B
155
8
Technical data of the basic unit
Technical data
AC 400/500 V / 3-phase / size 5 / 55 / 75 kW / 74 / 100 HP
MOVITRAC
®
MC07B (3-phase supply system)
0550-503-4-00
0750-503-4-00
Part number ("Safe stop" integrated)
829 527 1
829 529 8
INPUT
1)
1) The line and output currents must be reduced by 20% from the nominal values for V
line
= 3 × AC 500 V.
Nominal line voltage
V
line
3 × AC 380 – 500 V
Nominal line frequency
f
line
50/60 Hz ±5%
Nominal line current
(at V
line
= 3 × AC 400 V)
I
line
I
line 125
AC 94.5 A
AC 118.1 A
AC 117 A
AC 146.3 A
OUTPUT
Output voltage
V
O
3 × 0 – V
line
Recommended motor power 100% operation
Recommended motor power 125% operation
P
Mot
P
Mot 125
55 kW / 74 HP
75 kW / 100 HP
75 kW / 100 HP
90 kW / 120 HP
Nominal output current 100% operation
Nominal output current 125% operation
I
N
I
N 125
AC 105 A
AC 131 A
AC 130 A
AC 162 A
Apparent output power 100% operation
Apparent output power 125% operation
S
N
S
N 125
73.5 kVA
90.8 kVA
91.0 kVA
112.2 kVA
Min. perm. braking resistance
(4-quadrant operation)
R
BW_min
6
Ω
4
Ω
GENERAL INFORMATION
Power loss 100% operation
Power loss 125% operation
P
V
P
V 125
1700 W
2020 W
2000 W
2300 W
Type of cooling / cooling air consumption
Forced cooling / 360 m
3
/h
Current limitation
150% I
N
for at least 60 seconds
Unit terminal cross section / tightening torque
Terminals
70 mm
2
/ AWG00
14 Nm / 120 lb in
Dimensions
W × H × D
280 mm × 610 mm × 330 mm (11.0 in × 24.0 in × 13.0 in)
Mass
m
35 kg / 77 lb
280 (11.0)
140 (5.51)
590 (23.2)
330 (13.0)
610 (24.0)
7 (0.3)
P
i
f
kVA
Hz
n