Installation notes for basic unit – electrical aspects
Installation
lation spaces. When heeding the usual installation notes (40 °C/100 mm (3.94 in) space
above and below), cold-plate technology is not necessary.
A good thermal connection to the cooler is important for safe operation of the frequency
inverters:
• The contact area between cooler and frequency inverter has to be the size of the fre-
quency inverter cooling plate.
• Level contact surfaces are required, maximum deviation 0.05 mm (0.0002 in).
• Connect cooler and cooling plate with all necessary screw connections.
• The mounting plate must not exceed 70 °C during operation. This must be ensured
by the cooling medium.
• Cold plate installation is not possible with FHS or FKB.
4.2.7
Deactivating the EMC capacitors – size 0 only
Only electricians are allowed to convert the unit. Once converted, the unit must be
marked with the sticker provided in the accessory bag.
Proceed as follows to deactivate the EMC capacitors in the MOVITRAC
®
B frequency
inverter:
1. Open the unit:
– Remove
all
connectors.
– Remove the electronics shield clamp.
– Remove the housing retaining screw in the center of the housing front.
– Remove the housing.
DANGER
Severe or fatal injuries from electric shock.
• Disconnect the inverter from the power. Disconnect the DC 24 V supply and the line
voltage.
• Wait 10 seconds.
• Ensure that the unit is de-energized.
• Take appropriate measures to avoid electrostatic charges (use discharge strap,
conductive shoes, etc.) before removing the cover.
• Touch only the unit frame and the heat sink. Do not touch any electronic compo-
nents.