Installing accessories and options – electrical aspects
Installation
HF output filter connection without V
DC link
connection (PWM frequency only 12 or
16 kHz)
4.4.8
HD output chokes
• Install the output choke close to MOVITRAC
®
B beyond the minimum clearance.
• Always route all 3 phases (not PE!) through the output choke.
• If the cable is shielded, the shield should not be routed through the output choke.
In the case of the HD output choke, the cable must be wrapped around the choke 5
times.
9007199345067147
B
+R
X2/3
X1
9007199271903243
n = 5