Operating Instructions – MOVITRAC® B
55
4
Installing accessories and options – electrical aspects
Installation
4.4.19 Installation of FIO11B/21B, FSC11B/12B, FSE24B, DFP21B
You can enhance the basic units with the FIO11B/21B, FSC11B/12B and FSE24B mod-
ules.
Connection and
installation of front
modules
Always attach the option to the unit with the screw that is included in the delivery. For
size 0, mount the spacer bolt first. The bolt is already installed in sizes 1 and higher. The
screw connection ensures a high-frequency EMC connection between the basic unit
and the option.
18014398749591179
Connection/module type
FIO11B
FIO21B
FSC11B/12B
FSE24B
Analog
module
Digital
module
Communica-
tion
Communi-
cation
Analog input/output X40
Yes
No
No
No
Digital inputs X42
No
Yes
No
No
RS485 for diagnostics (RJ10) X44
Yes
Yes
Yes
Yes
RS485 terminal connection X45
Yes
No
Yes
No
SBus terminal connection X46
No
Yes
Yes
No
EtherCAT
®
connection (2 × RJ45) X30 No
No
No
Yes
X45
X46
1 2 3 4 5 6
H L
⊥
FSC11B
7
X44
S1
S2
OFF
ON
X45 X40
1 2 3 4 5
H L
⊥
FIO11B
X44
X46
X42
1 2 3 4 5 6
FIO21B
7
X44
X44
X47
RUN
ERR
SYS-F
X30 IN
X30 OUT
FSE24B
Ether
CAT
®
X47
1 2
FSE24B
X44
X30 IN X30 OUT
X45
X46
1 2 3 4 5 6
H L
⊥
FSC12B
7
X44
H L
⊥
Function
Terminal
Description
Data
FIO11B
FIO21B
FSC11B/
12B
FSE24B
Service
interface
X44
Via RJ10 plug con-
nector
For service purposes
only
Maximum cable length
3 m (10 ft)
Yes
Yes
Yes
Yes
RS485 inter-
face
X45:H
ST11: RS485+
Connected in parallel
with X44
Yes
No
Yes
No
X45:L
ST12: RS485–
X45:
⬜
GND: Reference
potential
Summary of Contents for Movitrac B
Page 2: ...SEW EURODRIVE Driving the world...
Page 259: ......