LEAK INDICATING UNIT
LAE 3-8
25/11/2019
- 6 -
Comply with relevant regulations regarding electric installation and
regulations for prevention of accidents.
DANGER:
From explosive vapor-air mixtures
Comply with explosion regulations, e.g., German Ordinance on Indus-
trial Safety and Health (Betriebssicherheitsverordnung, BetrSichV)
(and/or directive 1999/92/EC and the laws of the respective member
states resulting therefrom) and/or others.
3. Technical Data of the Indicating Unit
3.1 General
Data
Dimension and drilling pattern
see Chap. 7
Weight 5.4
kg
Storage temperature range
-30°C to +70°C
Operating temperature range
0°C to +40°C
Buzzer volume
>70 dB(A) in 1 m
Housing protection class
IP 40
3.2 Electrical
Data
Power supply
100 to 240 V AC, 50-60 Hz
Power input
44 W
Terminals 60(27)/61(28)/62,
Potential-free outputs
max. 1.5 A for 220 V DC/250 V AC
3.3 Field of Application
3.3.1 General
use
The indicating unit 3-8 has up to eight boards. Each of these boards
has three input channels.
Each channel has two terminals. When connected, a signal circuit is
closed between the terminals. If a VLX .. A-Ex is connected, only the
first channel can be used. All other channels have to be closed
(bridge).
If the signal circuit of the first channel is closed, the indicating unit is
in good state. If the signal circuit is interrupted, the alarm is triggered
at the LAE.
Note:
Unused channels in the indicating unit must be bridged.
In the event of an alarm, the internal buzzer sounds on the indicating
unit and indicator lights on the keypad light up.
The following applies to the alarm display on the keypad:
Safety/Technical Data