background image

Recommended wire For your reference

Safe carrying capacity of rubber or plastic insulated wire(1)

specification mm

nominal cross

section

mm2

Safe carrying capacity A

BX

BLX

BV

BLV

1*1.13

1

20

18

1*1.37

1.5

25

22

1*1.76

2.5

33

25

30

23

1*2.24

4

42

33

40

30

1*2.73

6

55

42

50

40

7*1.33

10

80

55

75

55

7*1.76

16

105

80

100

75

7*2.12

25

140

105

130

100

7*2.50

35

170

140

160

125

19*1.83

50

225

170

205

150

19*2.14

75

280

225

255

185

19*2.50

95

340

280

320

240

Note BX(BLX copper aluminum core rubber insulated wire or BV(BLV copper aluminum
core PVC plastic insulated wire widely used in 500V or less than 500V AC and DC power
distribution system. The temperature for the data listed in the above table is 35

the safe

carrying capacity value for the wire on single coved.

8.

8.

8.

8. Safety Instructions

Information for Your Own Safety

This manual does not contain all of the safety measures for operation of this equipment (module,
device) because special operating conditions, local code requirements or local regulations may
necessitate further measures. However, it does contain information which must be adhered to for
your own personal safety and to avoid damage to the equipment. This information is highlighted
by a warning triangle with an exclamation mark or a lightning bolt depending on the severity of the
warning.

Warning

Means that failure to observe the instruction can result in death, serious injury or considerable
material damage.

Summary of Contents for SGE-353-1Y-10100M

Page 1: ......

Page 2: ...62053 21 Frequency 50 60Hz Impulse constant 12000imp kWh Display LCD 6 2 Power consumption 2W 10VA Starting current 0 002Ib Working Temperature 20 55 Storage Temperature 25 70 Working voltage 0 9 1 1...

Page 3: ...this case the variable ratio has been fixed and not able to modify any more Note the button is inside the hole we suggest you to use auxiliary tool that could touch the inside button when set the rati...

Page 4: ...dication of B Phase C Power Indication of C Phase D Impulse Output Material Case Grey flame resistant ABS Terminal cover Grey flame resistant ABS Base Bottom Grey flame resistant ABS 4 Display 5 Conne...

Page 5: ...firmed by yourself fixed them in the location which are waiting for installation Put the meter into the upper Din Rail then push down the clip in the meter bottom see Fig 3 After the bottom of the met...

Page 6: ...Fig 6 is after installation Fig 6 Making the connection according to the wiring diagram see Fig 7 Fig 7 After connection use lead sealing to seal terminal cover see Fig 8 Fig 8...

Page 7: ...power distribution system The temperature for the data listed in the above table is 35 the safe carrying capacity value for the wire on single coved 8 8 8 8 Safety Instructions Information for Your O...

Page 8: ...ed personnel in the manual Subject to technical modifications without notice General Warning After removing the packaging make sure the integrity of the unit If in doubt don t use the equipment and co...

Reviews: